Obsnap Instruments Sdn Bhd
29A, Jalan SS 15/4C, 47500 Subang Jaya, Selangor, Malaysia.
+603-5621 5786
+603-5621 5829
+60122185651 (Enquiry)
+60162233687 (Vacancy)

3P4W Power Analyzer TES-3600

Previous 5 / 5 Next

3P4W Power Analyzer TES-3600 Harmonic Clamp Meter Electrical Inspection

Quantity
Add Quotation


Product Features
  • 10 Display Easy - to - View LCD Screen.
  • Connectors for 4 Current Sensing Clamps.
  • 1P2W, 1P3W, 3P3W2M & 3P4W Power Measurement.
  • True RMS Sensing.
  • Power KW, KVAR, KVA, PF,θ,Hz, &
    Energy KWh, KVARh & KVAh Measurement.
  • Phase sequency indicator function.
  • Backlight display function.
  • Manual Data Memory and Read (99 sets).
  • Data Logging (504KB Memory, 20,000 sets)
  • Programmable Trigger - Points and Start / Stop Time.
  • USB Optical Interface with three phase voltage /
    current Waveform display and Harmonic analysis.
  • Easy - to - use Push - Button Operation.
  • Light Weight, Portable Design.
Specification

q Voltage Measurement (V) :
Range Resolution Accuracy Input impedance Overload protection Nominal power system frequency
999.9V 0.1V ±(0.3%rdg±10dgts) (>50V) 2MΩ 1000Vrms Only 50Hz or 60Hz
q AC Current Trms Measurement (A) Autoranging :
Range Resolution Accuracy
(including current probe)
Current probe output Overload protection Nominal power system frequency
999.9A 0.1A ±(0.5%rdg±15dgts)
(>3A)
0.35mV/A 1000Arms Only 50Hz or 60Hz
q Active Power measurement P (KW) :
Range Resolution Accuracy
999.9KW 0.1KW ±1.0%rdg±20dgts
q Apparent Power measurement S (KVA) :
Range Resolution Accuracy
999.9KVA 0.1KVA ±1.0%rdg±20dgts
q Reactive Power measurement Q (KVAR) :
Range Resolution Accuracy
999.9KVAR 0.1KVAR ±1.0%rdg±20dgts
q Power Factor measurement (COSψ) :
Range Resolution Calculated Accuracy
0  ~  +1 0.001 ±3dgts
q Phase angle measurement (ψ) :
Range Resolution Calculated Accuracy
+90°~ 0°~ -90° 0.1° ±3dgts
 
q Frequency measurement (Hz) :
Range Resolution Accuracy Measurement source
60HZ 0.1Hz ±0.1%rdg±2dgts Voltage U1 > 50V
q Three Phase Sequency Detection :
Input voltage range Normal phase indication Reverse phase indication Measurement source
3P > 50V U1, U2 and U3
q Power Energy measurement (Wh, VAh, varh) :
Range Resolution Active power
accuracy
Timer interval Timer Accuracy
9.999K 0.001K Wh : ±1.0%rdg±20dgts
 
VAh : ±1.0%rdg±20dgts
 
varh : ±1.0%rdg±20dgts
1 sec ±50ppm
(25
, 77)
99.99K 0.01K
999.9K 0.1K
9.999M 0.001M
99.99M 0.01M
30.59M 0.1M
q Harmonic measurement (use only PC on line analyzer) :
Order Accuracy Harmonic Source No. of samples per period
1 ~ 31 ±3%THD U1, U2, U3 > 80V
 
I1, I2, I3 > 50A
64
q Waveform (use only PC on line displayed).
Select Phase A, B or C.
Select the Voltage and current waveform outputs.
 
General Specifications :
Size 235(L)x116(W)x54(H)mm  (9.3'Lx4.6'Wx2.1'H)
Operating Temperature and  Humidity 0to 50 (32 to 122) R.H. < 80% non-condensing
Storage Temperature and  Humidity -10to 60 (14to 140) R.H. < 70% non-condensing
Accessories  Instruction manual          Software CD-ROM / Optical USB interface
ƒDeluxe carrying case          Battery ( “AA” 1.5V x 8pcs )
AC adaptor (110Và12V ; 220Và12V) 
4pcs current clamp transducer (1, 2, 3, 4 cable length 3 meters)
  (1000A AC,  jaw opening 40mm)
4pcs crocodiles test leads (blue, yellow, red, black, wire length 3 meters)

Please leave your enquiry here, we will reply as soon as possible.